Multifunctional time relay CRME-101 (12-240V AC/DC, 1x16A_AC1) ETIMultifunctional time relay CRME-101 (12-240V AC/DC, 1x16A_AC1) ETI

Multifunctional time relay CRME-101 (12-240V AC/DC, 1x16A_AC1) ETI

Forget about routine monitoring! The ETI CRME-101 multifunctional time relay provides precise automation and reliable control of your systems. It will simplify everyday tasks, making processes more efficient and convenient.
Manufacturer ETI

Артикул:  2471557

In stock
Buy in 1 click
915,10 грн.

                                                                              Delivery

Self-pickup

Product delivery point

By courier in Kyiv - by arrangement.cool
<div style=
In Ukraine - according to the carrier's rates center;">(Free delivery when ordering for
from 3000 UAH. for some product groups)
                                                                           Guarantee

Exchange/return of goods within 14 days

Official warranty from
manufacturer

                                                                                              Payment

Cash, non-cash (including VAT).

PrivatBank, Oschadbank

Supply voltage: 12-240 V AC/DC
AC supply voltage frequency: 50-60 Hz
Allowable range of AC supply voltage: 0.8-1.1 Un
Allowable range of DC supply voltage: 0.9-1.2 Un
Power consumption: 2.5 VA / 1.5 W
Number of output contacts: 1 changeover (SPDT)
Rated current of output contacts: 16 A
Output contact application category: AC1
Rated voltage of output contacts: 250 V AC
Minimum switching power: 500 mW
Maximum switching power (AC1): 4000 VA
Maximum switching power (DC1): 384 W
Contact material: AgNi
Electrical durability: 10^5 cycles
Mechanical durability: 10^7 cycles
Number of functions: 10
Function A: ON-delay
Function B: OFF-delay
Function Bi: Single pulse after switching on
Function C: ON/OFF delay
Function Ci: Pulse after switching on, ON/OFF
Function D: Cyclic mode, start from ON
Function E: Cyclic mode, start from OFF
Function F: Single pulse after switching on with delay
Function G: Off-delay after closing the control contact
Function H: Off-delay after opening the control contact
Number of time ranges: 10
Time range 1: 0.1 s - 1 s
Time range 2: 1 sec - 10 sec
Time range 3: 6 sec - 60 sec
Time range 4: 1 min - 10 min
Time range 5: 6 min - 60 min
Time range 6: 0.1 h - 1 h
Time range 7: 1 h - 10 h
Time range 8: 10 h - 100 h
Time range 9: 0.1 day - 1 day
Time range 10: 1 day - 10 days
Minimum time setting interval: 0.1 sec
Maximum time setting interval: 10 days
Time setting accuracy: < 5%
Repeatability: < 0.2%
Temperature drift: < 0.01% / °C
Supply voltage drift: < 0.2%
Timekeeping accuracy: ± 1%
Power indicator: Green LED
Output status indicator: Red LED
Minimum control pulse width: 25 ms
Mounting type: DIN rail EN 60715
Enclosure width: 1 module (17.5 mm)
Enclosure height: 90 mm
Enclosure depth: 64 mm
Enclosure protection rating: IP40
Terminal protection rating: IP20
Enclosure material: Self-extinguishing plastic UL94-V0
Weight: 63 g
Cross-section of connected conductors (solid): 1x 2.5 mm² / 2x 1.5 mm²
Cross-section of connected conductors (stranded): 1x 2.5 mm² / 2x 1.5 mm²
Terminal tightening torque: 0.4 Nm
Operating temperature: -20 °C to +55 °C
Storage temperature: -30 °C to +70 °C
Relative humidity: 95% (non-condensing)
Installation altitude: up to 2000 m
Insulation strength (supply/output): 2.5 kV AC
Insulation strength (between open contacts): 1 kV AC
Conforms to standards: EN 61812-1, EN 61010-1
Electromagnetic compatibility: EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4

Add comment