Multifunctional time relay CRM-93 H 230V (3x8A_AC1) ETI
Артикул: 2470071
Delivery
Self-pickup
Exchange/return of goods within 14 days
Official warranty from
manufacturer
Cash, non-cash (including VAT).
PrivatBank, Oschadbank
Supply voltage tolerance: -15% / +10%
Supply voltage frequency: 50/60 Hz
Power consumption (AC 230 V): max. 4 VA (1.5 W)
Number of time functions: 10
Time function types: A, Ao, B, C, D, E, F, G, H, I
Number of time ranges: 10
Time setting ranges: 0.1 s - 1 s, 1 s - 10 s, 6 s - 60 s, 1 min - 10 min, 6 min - 60 min, 0.1 h - 1 h, 1 h - 10 h, 1 day - 10 days, 1 day - 10 days (cycle), 10 days (cycle)
Minimum time setting: 0.1 s
Maximum time setting: 10 days
Time setting accuracy: 5% (of the set value)
Repeat accuracy: 0.2% (of the set value)
Temperature drift: 0.05% / °C
Voltage drift: 0.1% / V
Number of output contacts: 3
Contact type: Changeover (CO)
Contact material: AgNi
Rated switching current (AC1): 3 x 8 A
Maximum peak current (AC1): 16 A (< 3 s)
Maximum switching voltage: 250 V AC / 24 V DC
Minimum switching current: 10 mA
Minimum switching voltage: 12 V AC/DC
Maximum switching power (AC1): 2000 VA
Electrical life (AC1): 10 ^ 5 cycles (at 8 A)
Mechanical life: 3 x 10 ^ 7 cycles
Control input type (S): Potential-free contact
Minimum pulse width at input S: 25 ms
Power indication: Green LED
Output status indication: Red LED (3 pcs.)
Operating temperature range: -20 °C to +55 °C
Storage temperature range: -30 °C to +70 °C
Relative humidity: 95% (non-condensing)
Altitude: up to 2000 m
Mounting type: On a 35 mm DIN rail
Width: 17.5 mm
Height: 90 mm
Depth: 64 mm
Weight: 64 g
Protection class of front panel: IP40
Protection class of terminals: IP20
Cross-section of connected conductors (single-core): max. 2.5 mm²
Cross-section of connected conductors (stranded): max. 1.5 mm²
Maximum tightening torque of terminals: 0.5 Nm
Insulation strength: 2.5 kV (between supply and contacts)
Overvoltage category: III
Pollution degree: 2
Conformity to standards: EN 61812-1, EN 61010-1