Voltage stabilizer Eleks Gerts-PRO U 36-3/125 v3.0
The features of this stabilizer include a dual LED indicator per phase, a linear loading strip, a mechanical transit (bypass), a floor-standing design, input and output filters for protection against high-frequency interference, and silent operation due to the use of toroidal transformers and thyristor keys.
If it is necessary to obtain a voltage different from 220 V at the stabilizer output, Hertz has a function for adjusting this value in the range of 200-230 V. In manual mode, you can change the output voltage in 1 V increments. In this case, the changes will be applied to all phases simultaneously.
The Hertz stabilizer has the ability to manually adjust the lower shutdown threshold (60-135 V). This function is in demand for loads with high inrush currents, which may experience a significant voltage drop and emergency shutdown of the stabilizer upon startup. When this option is activated, the stabilizer will allow you to start any motor or pump within a minute, even with a voltage drop of up to 60 V in the network.
The built-in phase synchronization mode will instantly disconnect a three-phase load, protecting it from voltage interruptions and power failures in the phases (one or two). This function has manual control and can therefore be disabled at any time. In this case, the phases will operate independently of each other.
It is recommended to install and operate the GERTS-PRO U 36-3/125 v3.0 stabilizer in dry and heated rooms. This device is designed for floor mounting. Connection of the
Артикул: LP16314
Delivery
Self-pickup
Exchange/return of goods within 14 days
Official warranty from
manufacturer
Cash, non-cash (including VAT).
PrivatBank, Oschadbank
| Key type | thyristor |
| Operating current, A | 3×125 |
| Rated power, VA/W | 83000/83000 |
| Number of stabilization stages | 36 |
| Stabilizer efficiency not less than, % | 98 |
| Power consumption at idle no more than, W | 20 |
| Rated output voltage, V | 220 |
| Minimum operating input voltage, V | 100 |
| Maximum operating input voltage, V | 280 |
| Output voltage adjustment, V | 200-230 |
| Lower shutdown threshold adjustment, V | 60-135 |
| Stabilization accuracy, % | 1 |
| Response time to input voltage change, ms | 20 |
| Power supply frequency, Hz | 45-65 |
| Input current and full load measurement power | yes |
| Short-circuit and overload current limitation | input circuit breaker with C-characteristic of electromagnetic protection |
| Electronic Bypass | yes |
| Network and stabilizer status analyzer | yes |
| Duplicate overvoltage protection | yes |
| Microcontroller control | yes |
| Input choke | yes |
| Output choke | yes |
| Protection against overheating | yes |
| Minimum cross-section of cable cores for connection, mm² | 16 |
| Maximum cross-section of cable cores for connection, mm² | 40 |
| Forced cooling | two-speed fan |
| Length, mm | 780 |
| Width, mm | 385 |
| Height, mm | 1280 |
| Warranty, months | 36 |
| Weight, kg | 255 |
| Volume, cubic meters | 0.384384 |