Voltage stabilizer Eleks Amper U 12-1/50 v2.1
The single-phase voltage stabilizer Ampere U 12-1/50 v2.1 (standard) is designed for operation in electrical networks with voltage fluctuations from 145 to 275V. In this range, the device is guaranteed to produce an output voltage within 220±3.5%, which is ensured by using 12 stages of stabilization. The rated power of this model is 11 kW, which corresponds to the operating current of the 50 A circuit breaker on it.
The features of this stabilizer include a dual LED screen, a linear loading strip, the presence of an electronic transit (bypass), a convenient location of the terminal block for connection on the rear of the case, and silent operation due to the use of thyristors as power keys.
The Ampere V 12-1/50 v2.1 stabilizer has the ability to manually adjust the lower shutdown threshold (60-135V). This feature is useful for loads with high inrush currents, which can cause a significant voltage drop and emergency shutdown of the stabilizer. When this option is activated, the stabilizer will start any engine or pump within a minute, even if the voltage drops to 60V.
It is recommended to install and operate the Ampere V 12-1/50 v2.1 stabilizer in dry, heated areas. When wall-mounted, it is recommended to install it vertically (with the fans facing up), leaving 10-15 cm of space above and below for cooling. Connection is made to existing wiring via a terminal block.
Артикул: LP16920
Delivery
Self-pickup
Exchange/return of goods within 14 days
Official warranty from
manufacturer
Cash, non-cash (including VAT).
PrivatBank, Oschadbank
| Key type | thyristor |
| Operating current, A | 50 |
| Rated power, VA/W | 11000/11000 |
| Number of stabilization stages | 12 |
| Stabilizer efficiency not less than, % | 98 |
| Power consumption at idle no more than, W | 35 |
| Rated output voltage, V | 220 |
| Minimum operating input voltage, V | 100 |
| Maximum operating input voltage, V | 295 |
| Lower trip threshold adjustment, V | 60-135 |
| Stabilization accuracy, % | 3.5 |
| Response time to input voltage change, ms | 20 |
| Power supply frequency, Hz | 45-65 |
| Input current and apparent power measurement | yes |
| Short-circuit and overload current limitation | input circuit breaker with B-characteristic of electromagnetic Protection |
| Electronic Bypass | yes |
| Network and Stabilizer Status Analyzer | yes |
| Duplicate Overvoltage Protection | yes |
| Microcontroller Control | yes |
| Input Choke | yes |
| Output Choke | no |
| Overheating Protection | yes |
| Minimum Cross-Section of Cable Cores for Connection, mm² | 10 |
| Maximum Cross-Section of Cable Cores for connection, mm² | 40 |
| Forced cooling | two-speed fan |
| Length, mm | 295 |
| Width, mm | 165 |
| Height, mm | 530 |
| Warranty, months | 36 |
| Weight, kg | 26 |
| Volume, cubic meters | 0.025798 |