Surge arrester ETITEC ML T123 300/12.5 (3+1, 4p, TT) ETISurge arrester ETITEC ML T123 300/12.5 (3+1, 4p, TT) ETI

Surge arrester ETITEC ML T123 300/12.5 (3+1, 4p, TT) ETI

Protect your valuable equipment from damaging power surges with the ETITEC ML T123 surge protector. It will reliably keep your equipment operational, preventing costly breakdowns and downtime. Invest in the longevity and stability of your electrical system. Provide peace of mind and confidence in the safety of your home or business.
Manufacturer ETI

Артикул:  2440671

In stock
Buy in 1 click
7916,06 грн.

                                                                              Delivery

Self-pickup

Product delivery point

By courier in Kyiv - by arrangement.cool
<div style=
In Ukraine - according to the carrier's rates center;">(Free delivery when ordering for
from 3000 UAH. for some product groups)
                                                                           Guarantee

Exchange/return of goods within 14 days

Official warranty from
manufacturer

                                                                                              Payment

Cash, non-cash (including VAT).

PrivatBank, Oschadbank

Device type: Combined surge arrester (SPD)
SPD protection class: Type 1 + Type 2 + Type 3
Earthing system: TT
Pole configuration: 3+1 (3 phases + neutral)
Nominal system voltage (Un): 230/400 V AC
Maximum continuous working voltage (Uc L-N/L-PE): 300 V AC
Maximum continuous working voltage (Uc N-PE): 300 V AC
Lightning impulse current (Iimp L-N/L-PE) (10/350 μs): 12.5 kA
Lightning impulse current (Iimp N-PE) (10/350 μs): 50 kA
Total lightning impulse current (Itotal) (10/350 μs): 50 kA
Nominal discharge current (In L-N/L-PE) (8/20 μs): 20 kA
Nominal discharge current (In N-PE) (8/20 μs): 50 kA
Maximum discharge current (Imax L-N/L-PE) (8/20 μs): 40 kA
Maximum discharge current (Imax N-PE) (8/20 μs): 100 kA
Voltage protection level (Up L-N): < 1.5 kV
Voltage protection level (Up N-PE): < 1.5 kV
Response time (ta): < 25 ns
Maximum short-circuit current (Isccr): 50 kA
Required back-up fuse (max): 160 A (gG)
Indication Status: Visual (green/red)
Remote signaling: No
Operating temperature range: -40...+80 °C
Protection class: IP20
Cross-section of connected conductors (rigid): 1.5-35 mm²
Cross-section of connected conductors (flexible): 1.5-25 mm²
Mounting type: On a 35 mm DIN rail
Width: 4 DIN modules
Housing material: Thermoplastic, self-extinguishing UL94 V-0
Conformity to standards: IEC 61643-11, EN 61643-11