Surge arrester ETITEC EM T12 PV 1100/6.25 Y (for PV systems) ETI
Артикул: 2440580
Delivery
Self-pickup
Exchange/return of goods within 14 days
Official warranty from
manufacturer
Cash, non-cash (including VAT).
PrivatBank, Oschadbank
Application: PV systems (photovoltaic)
Configuration: Y-scheme
Maximum continuous working voltage (Uc PV): 1100 V DC
Nominal discharge current (In (8/20 μs)): 20 kA
Maximum discharge current (Imax (8/20 μs)): 40 kA
Lightning impulse current (Iimp (10/350 μs) per pole): 6.25 kA
Total lightning impulse current (Iimp total (10/350 μs)): 12.5 kA
Voltage protection level (Up) at In: ≤ 3.2 kV
Voltage protection level (Up) at Iimp: ≤ 4.0 kV
Permissible short-circuit current (Isccr): 2000 A (at 1100 V DC)
Response time: < 25 ns
Operating temperature range: from -40 ° C to + 80 ° C
Enclosure protection rating: IP20
Mounting: On a 35 mm DIN rail
Maximum conductor cross-section (rigid): 35 mm²
Maximum conductor cross-section (flexible): 25 mm²
Status indication: Optical (green - OK, red - needs to be replaced)
Remote signaling: Yes (potential-free changeover contact)
Remote signaling contact parameters: 250 V AC / 0.5 A
Enclosure material: Thermoplastic, self-extinguishing UL94 V-0
Number of DIN modules: 3 module
Width: 54 mm
Height: 90 mm
Depth: 71 mm
Weight: 0.45 kg
Standards: EN 50539-11, IEC 61643-31
Protection principle: Metal oxide varistor (MOV)
Protective element: Plug-in module
Thermal disconnector: Built-in