Number of poles: 3 P
Polar system: 3 P
Direction switch: no
Integrated motor drive: no
Rated connection voltage U8 (AC0) insulation voltage Ui: 1000 V
Rated impulse withstand voltage Uimp: 8000 V
AC21 AC load in category A: 3200 A
AC21 AC load in category B: 3200 A
Permissible load AC22 Permissible load category B: 800 A
Rated operational current (AC23), category A: 800 A
Rated operational current (AC23), category B: 800 A
Rated Short-time withstand current Icw: 50 1s: 50 kA
Rated power below 660 V, 50 Hz: 185 kW
Active power below 380/415 V, 50 Hz: 450 kW
Rated switching power for rated voltage 400 V for kW1: rated current: 340 W
Total power loss for rated current: 1020 W
Mechanical durability (number of cycles): 4000
Cross-section in wire: 2x300 mm²
Connection type: 8' mm²
Additional motor drive: no