Number of poles: 3 P
Pole type: 3 P
Frequency: 50/60 Hz
Rated operational voltage Ue: 400 V0 0 Type
Input voltage type 1: AC
Rated impulse withstand voltage: 6000 V
Rated operational current in AC21 category A: 100 A
Rated operational current in AC21 category B: 100 A<2 /0 />Acceptable current rating of AC22 category B: 100 A
Rated operational current in AC23 category A: 40 A
Acceptable current rating of AC23 category B: 40 A
Short-circuit current with gI-gG fuses: 1200 A <0 1692 A
Rated short-circuit withstand power Icm at 415V AC according to IEC 60947-3: 1692 A
Rated short-time withstand current 1s: 1.2 kA
Rated thermal current outside enclosures: 100 A < W
Total power loss under IN: 16.5 W
Electrical strength at rated load in operating cycles AC21: 2500
Electrical life at rated load in AC22 in operating cycles: 2500 <0 /000 of the installed product: 68 mm
Height of the installed product: 83 mm
Width of the installed product: 52.5 mm
Tightening torque: 3.6 Nm
Cellular clamping position: in-line
Cross-section connection rigid cable: 6/50mm²
Cross-section connection flexible cable: 6/35mm2
Connection type: with screw
Number of contacts NO: 3
IP protection index: IP20
Altitude above sea level: 2000 m
Storage temperature: from -40 to 80°C