Hager H630 Circuit Breaker. In=400A. 3 points, 50kA. LSI, HND400H
Артикул: HND400H
Delivery
Self-pickup
Exchange/return of goods within 14 days
Official warranty from
manufacturer
Cash, non-cash (including VAT).
PrivatBank, Oschadbank
Enclosure type: Fixed built-in
Number of poles: 3 P
Pole type: 3P3D
Complete device with protection unit: yes
Trip unit: LSI
Integrated earth fault protection: no0
Built-in drive Hz
Rated operational voltage Ue: 220/690 V
Rated insulation voltage: 800 V
Rated impulse withstand voltage: 8000 V
With live release: no
Correction factor 2 />Correction factor of the rated current for 3 devices placed side by side: 1
Correction factor of the rated current for 4 and 5 devices placed side by side: 1
Correction factor of the rated current for 6 devices placed side by side: 1
Power loss per pole at 0.63*V: 8.3 W
Power loss per pole at 0.8*V: 13.3 W
Total power loss under IN: 62.4 W
Total power loss at 0.63 * V: 24.8 W * 8 W
Total in />Thermal protection tripping time: 5/10/11/19/21/29 ms
Opening response time: 10 ms
Magnetic tripping delay time: 100 - 200 ms
Electrical endurance in number of cycles: 1000
Tightening torque: 22 Nm
DIN rail mounting with additional adapter: no
Cross-sect. connection Rigid cable: 35/240mm2
Cross-section connection flexible cable: 35/240mm2
Connection: Front connection
Connection type: Terminal
Magnetic protection, installation xIN: 2.5/5/10
Magnetic adjustment range: 2240/2800/3500/45 />Use category: A
IP protection index: IP4X
Storage temperature: -35 to 70 ° C
Protection against air humidity: for all climatic conditions