Enclosure type: Fixed built-in
Number of poles: 3 P
Pole type: 3P3D
Complete device with protection unit: yes
Trip unit: TM A / A
Integrated earth fault protection: no
V 50/60 Hz
Rated operating voltage Ue: 220/415 V
Rated insulation voltage: 800 V
Rated impulse withstand voltage: 8000 V
With live release: no
Factor: 1
Rated current correction factor for 3 devices located next to each other: 1
Rated current correction factor for 4 and 5 devices located next to each other: 1
Rated current correction factor for 6 powerful devices next to each other: 1
Losses />Power loss per pole at 0.63*V: 3.3 W
Power loss per pole at 0.8*V: 5.3 W
Total power loss under IN: 24.8 W
Total power loss at 0.63*V: 9.9 W: 15.9 W
Response time when opening: 10 ms
Electrical endurance in number of cycles: 1000
Number of mechanical operations: 4000
Tightening torque: 12 Nm
DIN rail mounting with additional adapter. rigid cable: 35/185 mm²
Cross-section connection Flexible cable: 35/150mm²
Connection: Front connection
Connection type: Terminal
Magnetic adjustment range: 600/800/1000/1300 A
Use category: A
IP protection index: IP4X C
Protection against air humidity: for all climatic conditions