Hager circuit breaker x160. In=160A. 3 points. 40kA. Trigger/Mfix., HNA160H
Артикул: HNA160H
Delivery
Self-pickup
Exchange/return of goods within 14 days
Official warranty from
manufacturer
Cash, non-cash (including VAT).
PrivatBank, Oschadbank
Enclosure type: Fixed built-in
Number of poles: 3 P
Pole type: 3P3D
Complete device with protection unit: yes
Disconnection unit: TM A / F
Integrated earth fault protection: no
Built-in 50/60 Hz
Rated operational voltage Ue: 220/415 V
Rated insulation voltage: 690 V
Rated impulse withstand voltage: 8000 V
With live release: no 1
Rated current correction factor for 3 devices placed next to each other: 1
Rated current correction factor for 4 and 5 devices placed next to each other: 1
Rated current correction factor for 6 powerful devices next to each other: 1
Losses />Power loss per pole at 0.63*V: 5.7 W
Power loss per pole at 0.8*V: 8.9 W
Total power loss under IN: 43.8 W
Total power loss at 0.63*V: 17.1 W<: 26.7 W
Response time when opening: 10 ms
Electrical endurance in number of cycles: 1000
Number of mechanical operations: 4000
Tightening torque: 6 Nm
DIN rail mounting with additional adapter. Rigid cable: 4/95 mm²
Cross-section connection Flexible cable: 4 / 70 mm²
Connection: Front connection
Connection type: with screw
Magnetic regulation range: 1600 A
Use category: A
IP protection index: IP4X<0 / ° C from air: -35 all climatic conditions