Rated reactive power (Q_n) at 440V, 50Hz: 35 kvar
Rated reactive power (Q_n) at 230V, 50Hz: 20 kvar
Rated reactive power (Q_n) at 500V, 50Hz: 40 kvar
Rated reactive power (Q_n) at 525V, 50Hz: 45 kvar
Rated reactive power (Q_n) at 690V, 50Hz: 50 kvar
Rated operating voltage (U_e): up to 690 V AC
Rated operating current (I_e) at 400V, 50Hz: 43 A
Rated operational current (I_e) at 440V, 50Hz: 46 A
Rated operational current (I_e) at 500V, 50Hz: 52 A
Rated operational current (I_e) at 525V, 50Hz: 55 A
Rated operational current (I_e) at 690V, 50Hz: 42 A
Maximum peak making current (I_p): 100 x I_e
Rated insulation voltage (U_i): 690 V AC
Rated impulse withstand voltage (U_imp): 6 kV
Rated frequency: 50/60 Hz
Number of main poles: 3
Built-in auxiliary contacts: 1 NO
Control circuit voltage (voltage coils): 24V AC, 48V AC, 110V AC, 230V AC, 400V AC (specified in the full article number)
Mechanical durability: 3 x 10 ^ 6 cycles
Electrical durability (AC-6b): 1 x 10 ^ 5 cycles
Operating temperature range: -25 ... + 55 ° C
Storage temperature range: - 50 ... + 70 ° C
Degree of protection: IP20
Mounting type: DIN rail 35 mm, screw fastening
Cross-section of main circuit conductors (solid / stranded): 1.5 - 35 mm²
Cross-section of main circuit conductors (flexible with ferrule): 1.5 - 25 mm²
Cross-section of control circuit conductors (solid / stranded): 0.5 - 4 mm²
Cross-section of control circuit conductors (flexible with ferrule): 0.5 - 2.5 mm²
Tightening torque of main terminals: 3.5 Nm
Tightening torque of control circuit terminals: 1.2 Nm
Coil power consumption (turn-on): 6.5 VA
Coil power consumption (holding): 5 VA
Power loss per pole: 4.5 W
Recommended short-circuit protection (gG fuse): 100 A
Width: 70 mm
Height: 85 mm
Depth: 104 mm
Weight: 0.76 kg
Conformity to standards: IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1
Material contacts: AgSnO2